SECTION 9: VENTING
21 of 33
FIGURE 19: Vertical Venting
9.7 Condensate Tee Assembly
The condensate tee assembly is composed of a tee,
draincap, and condensate trap.
If the system is designed in the condensing mode, then
the installation of a condensate tee assembly is
required. The condensate tee assembly, must be
installed on the inlet side of the pump assembly if there
is horizontal venting of the pump, See Page 22, Figure
20.
A condensate drain on the discharge side is required
if there is vertical venting of the pump or if there is a
vertical rise in the discharge line away from the
pump. See Page 22, Figure 21.
The condensate tee assembly in the discharge line
can be eliminated if the discharge line is horizontal
through the wall and pitched down at least 1/4" per
10' (6 mm per 3 m). This arrangement will permit
drainage of condensate through the pump and out-
side via the horizontal (pitched) discharge line.
Description Part Number
Tee 6" (15 cm) 01330204
Vent Cap 6" (15 cm) 90502302
Drain Cap 6" (15 cm) 02718852