Installation manual

SECTION 3: INSTALLATION
13
3.7 Indoor Sensor Placement
The sensor measures the air temperature in the
building. It is important that the sensor is located in
an area within the heated zone at occupant level. For
the most accurate results, sensors should be
mounted on an inside wall, away from any air vents
or other sources of heat and cold. In order to avoid
short system cycles and inaccurate temperature
readings, do not mount sensors under the first
section of radiant tube (first 10’ (3 m) section of tube
after the burner). The sensors are suitable for
direct surface mounting or 4" x 2 1/8" junction box
mounting.
FIGURE 9: Indoor Sensor Mounting
3.7.1 Indoor Sensor Mounting
Remove the cover of the sensor by the two 1/16"
allen screws, located in the lower corners of the
cover. To gain access to the top mounting hole
remove the plug-in LCD display. To remove the LCD
display, grasp the green plug-in board at the lower
corners and gently pull the board away from the
sensor back plate. See Figure 9. After removing the
plug-in LCD display from its socket, secure the
sensor to the wall or junction box using the screws
provided. Replace the plug-in LCD display and
secure the cover with the two 1/16" allen screws.
SEN SET O/R
-+
Mounting
Hole
Plug-in LCD
Display
(grasp here
to unplug)
Mounting
Hole
Setback
Override
Button
Setpoint
Adjustment
Slide bar