Service manual

ROBERTS-GORDON SECTION 11: WIRING pg 31
Figure 29. EV Panel Box Label
Power
Supply
Vacuum
Pump
Zone 1
Burners
Zone 2
Burners
Zone 3
Burners
Zone 4
Burners
Thermostats
Zone 1 Zone 2 Zone 3 Zone 4
Zone 1
Zone 2
Zone 3
Zone 4
Smart Set (Optional)
Night Set Back(Optional)
Wiring for Burners
Thermostats
Vacuum Pump
Optional Outside Air Blower
Gnd.
Hot Neut. Hot Neut. Hot Neut. Hot Neut. Hot Neut. Hot Neut. COM T 1 T 2 T 3 T 4 MBR
MBR
COM
Smart
Set
Night
Set
Back
Fused
Disconnect
Switch
120V-60 Hz
Supply Circuit
(20 Amps)
Centrifugal Motor Interlock
(only 3/4-hp motor)
Vacuum Proving
Switch
Load Relay
(120V Coil)
Outside Air
Blower
If connecting
Outside Air Blower,
break this connection
120V-60 Hz
Supply Circuit
(20 Amps)
© P/N 91016500 Rev. A
Printed in USA
Electrical Shock Hazard
Disconnect electrical power before servicing.
Failure to follow these instructions will result in death or electrical shock.
WARNING
Notes:
1. A load relay is required for the (optional) outside air
blower on either
Vantage
®
EV
or
CoRayVac
®
systems.
2. The vacuum proving switch is required for all systems.
3. Low voltage or pilot duty thermostats should be used.
Thermostats that require a power supply of 24V to
operate must not be used because control voltage
available on the circuit board is only 12VDC.
4. For more in-depth information regarding the installation
or operation of this ROBERTS GORDON
®
heating
system, consult the Installation Manual provided, or
contact your local Roberts-Gordon representative.
Hz
V
A
60
< 12120
THIS PANEL IS CERTIFIED AS A COMPONENT PART OF
ROBERTS GORDON
®
CoRayVac
®
AND
Vantage
®
EV
INFRARED
HEATING EQUIPMENT.
ELECTRICAL RATING:
APPROVED