SECTION 10: SERVICING INSTRUCTIONS
23 of 27
10.3 Maintenance Checklist
Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON
®
equipment must be performed by a contractor
qualified in the installation and service of equipment
sold and supplied by Roberts-Gordon LLC and
conform to all requirements set forth in the
ROBERTS GORDON
®
manuals and all applicable
governmental authorities pertaining to the
installation, service, operation and labeling of the
equipment. To help facilitate optimum performance
and safety, Roberts-Gordon LLC recommends that a
qualified contractor conduct, at a minimum, annual
inspections of your ROBERTS GORDON
®
equipment and perform service where necessary,
using only replacement parts sold and supplied by
Roberts-Gordon LLC
.
.
System Tubing and Vent
Pipe
Venting must be intact. Using a flashlight, look for obstru ctions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust or blockage.
Remove any carbon deposits or scale using a wire brush.
Replace pipe if there are any holes due to corrosion. Seal any gaps in venting
to prevent condensate leakage.
Pump Scroll, Impeller and
Motor
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
Check for corrosion, if any parts have corroded through, replace as neces-
sary.
Ensure all hex nuts are tight for proper seal.
Suspension Points Make sure the pump is hanging securely.
Look for signs of wear on the mounting angles, wall mounting points or ceiling
mounting points.
Pump Boot Inspect pump boot at pump inlet and outlet for cracking or deterioration.
Replace if cracks are found.
Ensure band clamps are tight at all connection points.
Condensate Trap, Drain
Cap
Check connection of tee to drain cap and between tee and condensate trap.
Seal connections between tee and drain cap to prevent condensate leakage.
Screw condensate trap tightly into drain cap or p
ump inlet assembly to pre-
vent leakage.
Condensate trap should be filled with water.
Pressure Switch Ensure that wiring is intact. Check silicone hose for cracks.
Ensure secure connection between pressure switch and barbed fitting.
Safety Labels Product safety signs or labels should be replaced by the product user when
they are no longer legible. Please contact Roberts-Gordon LLC or your ROB-
ERTS GORDON
®
independent distributor to obtain replacement signs or
labels. See Page 2, Figure 1.