Service manual
EP-200 SERIES PUMP INSTALLATION, OPERATION AND SERVICE MANUAL
20 of 27
Step 3: Choose the condensate neutralization
tube
Choose the condensate neutralization tube which is
closest to and higher than the calculated gal/h value.
For this example, the total condensate is 1.8 (gal/h),
the condensate neutralization tube which is closest
to and higher than the calculated gal/h value is P/N
01327002.
NOTE: Condensate neutralization tubes must be
replaced yearly (every 2000 operating hours) or
check condensate water pH level. If it is below pH 6,
replace tube.
To order replacement, see the chart below:
FIGURE 19: Condensate Neutralization Tube
Calculated gal/h Description Part Number
Less than 2 Condensate Neutralization Tube 200 01327002
Less than 6 Condensate Neutralization Tube 600 01327003
Less than 10 Condensate Neutralization Tube 1000 01327004
Less than 20 Condensate Neutralization Tube 2000 01327005
Description Part Number
Condensate Neutralization Tube 200 01327002
Condensate Neutralization Tube 600 01327003
Condensate Neutralization Tube 1000 01327004
Condensate Neutralization Tube 2000 01327005
Refill, Condensate Neutralization Tube 600 01327007
Refill, Condensate Neutralization Tube 1000 01327008
Refill, Condensate Neutralization Tube 2000 01327009
Calculated gal/h Description Part Number
Less than 2 Condensate Neutralization Tube 200 01327002
Less than 6 Condensate Neutralization Tube 600 01327003
Less than 10 Condensate Neutralization Tube 1000 01327004
Less than 20 Condensate Neutralization Tube 2000 01327005