Service manual
EP-200 SERIES PUMP INSTALLATION, OPERATION AND SERVICE MANUAL
12 of 27
SECTION 7: PUMP MOUNTING INSTRUCTIONS 7.1 Wall Mounting
The standard method of mounting the EP-200 pump
is on an outside wall and venting directly through the
wall.
The pump may be mounted by using mounting
angles as shown in Figure 9. The two mounting
angles form a mounting platform to which the pump
will be attached.
Attach the mounting frame to the wall using anchors.
Select an anchor that will give equal to or greater
than 2000 lb ultimate pull-out strength.
FIGURE 9: Wall Bracket Assembly
FIGURE 10: Wall Mounting Angle Assembly
Mounting
Angle
Hex Bolt
Flat Washer
Lockwasher
Hex Nut
Flat Washer
Description Part Number
Mounting Angle 01365000
Hex Bolt 5/16" x 3/4" 93413912
Flat Washer 95211600
Lockwasher 96411600
Hex Nut 92113900
NOTE: Typical assembly shown.
Two (2) assemblies per
each pump required.
7"
(178 mm)
11.5"
(292 mm)