9.5 Vertical Venting
Vent length should be limited to less than 30' (9 m).
If using vent lengths greater than 30' (9 m),
condensation will form in the vent pipe. Insulation
and additional sealing measures will be required.
Length of flue pipe is equal to total of vertical and
horizontal length.
FIGURE 17: Vertical Venting
Approved
Vent Cap
Approved
Thimble
(if applicable)
2' (.6 m)
Minimum
Silicone
Rubber Ring
Approved
Thimble
(if applicable)
1" (2.5 cm)
P. V. C
Tee
Drain Cap
Description Part Number
Tee 4" (10 cm) 01330203
Vent Cap 4" (10 cm) 90502300
Drain Cap 4" (10 cm) 02718851