SECTION 7: AIR SUPPLY
11
SECTION 7: AIR SUPPLY
7.1 Room Sealed Installation
When installed as a room sealed heater, the air for
combustion is drawn in from outside the building. It
is important to ensure that there is adequate
ventilation to provide air for the distribution fan/s.
Room sealed installation kit includes:
Air Adapter
•Hose
•Clamps
7.2 Open Flued Installation
It is important to ensure that there is adequate air
supply at all times for both combustion and heating
requirements in accordance with local and national
codes.
7.2.1 Heaters Installed Within the Heated Space
Where the volume of the heated space is greater
than 4.7 m
3
per kilowatt of total rated heat input and
the air change rate is at least 0.5/h, additional high
and low level ventilation will not be required.
For a building having an air change rate less than
0.5/h, ventilation will be necessary in accordance
with local and national codes. Ventilation direct to
outside must be provided as follows:
Heaters up to 70 kW heat input 5.0 cm
2
per kW
of rated heat input
7.3 Building Ventilation
Where ventilation is required, air must be taken from
an outside point where it is not likely to be
contaminated or obstructed.
Where natural ventilation is used, suitable ventilation
with outside air at low level must be provided in
accordance with Section 7.2.1 and local and national
codes.
Where mechanical ventilation is used, extract rate
must be 5% - 10% less than the inlet rate. The
mechanical ventilation must be interlocked with the
burner on the CTU heater.
ODELJAK 7: DOVOD VAZDUHA
ODELJAK 7: DOVOD VAZDUHA
7.1 Gasna instalacija gasnog potrošača tipa C
Kada se instalira kao sobno grejno telo, vazduh za
sagorevanje se dovodi spolja. Važno je obezbediti
adekvatnu ventilaciju kako bi se obezbedio vazduh
za ventilator(e).
7.2 Gasna instalacija gasnog potrošača tipa B
Važno je obezbediti odgovarajući dotok vazduha sve
vreme za sagorevanje, odnosno grejanje kako je
predviđeno uslovima, to jest u skladu sa nacionalnim
i lokalnim propisima. Kada se instalira na ovaj način,
dovod vazduha do grejnog tela pretpostavlja
postojanje i blago otpornog (propusnog) završetka
kako bi se sprečio mogući ulazak krupnijih materija/
komada. Pogledatistranu 12, dijagram 6.
7.2.1 Grejan tela instalirana unutar prostora koji
se greje
Tamo gde je zapremina prostora koji se zagrejava
veća od 4.7 m3 po kilovatu ukupnog unosa toplote i
gde stopa vazdušne promene iznosi najmanje 0.5/h,
dodatni nivo ventilacije nije neophodan.
Gde je stopa vazdušne promene manja od 0.5/h
neophodno je obezbediti ventilaciju u skladu sa
lokalnim i nacionalnim propisima. Ventilacija
usmerena prema spolja obezbeđuje se na sledeći
način:
• Zagrejači do 70 kW 5.0 cm2 po kW stope
unosa toplote
7.3 Ventilacija zgrade
Vazduh za potrebe ventilacije, gde je potrebno,
uzima se iz spoljnjeg izvora koji nije kontaminiran i iz
koga je to moguće neometano činiti.
Gde se koristi prirodna ventilacija, odgovarajuća
ventilacija vazduhom spolja (na nižem nivou) mora
biti u skladu saodeljkom 7.2.1i lokalnim i nacionalnim
propisima.
Gde se koristi prinudna ventilacija, odsisavanje mora
biti za 5 do 10% manje od dovoda svežeg vazduha.
Prinudna ventilacija mora biti povezana sa radom
CTCU gorionikom (tj. mora raditi kada i gorionik).