CTCU KÜTTESEADME PAIGALDUSE, KASUTUSE JA HOOLDUSE KÄSIRAAMAT
24
14.3 Leegi jälgimissüsteemi veaotsing
Repair or replace as
necessary.
If problems persist, contact
ROBERTS GORDON
®
at
Tel: +44 (0) 1902 498733
www.rg-inc.com
Control box faulty.
Replace with correct type.
Use Section 14.1 to
trace the fault.
Heater Operating
TROUBLESHOOT ENDS.
No
Repair or replace as
necessary.
Is inlet burner gas pressure
correct? Is live and neutral
polarity correct? Is
flame probe circuit correct?
Is there a current flowing in the
flame probe circuit with no
flame present?
Ye s
No
Does lockout occur when
there is a flame present?
Ye s
Is the connecting lead
damaged? Is the flame probe
damaged or touching earthed
components?
No
Is the flame present and
at least 1 µA DC flame
current?
Connect a DC ammeter in
series with the flame probe.
Ye s
No
Ye s
Ye s
No
START
MÄRKUS: Leegisondi minimaalne vool 1 μA DC. Tüüpiline leegisondi vool 3-5 μA (alalisvool).
Leegi voolu mõõtmiseks ühendage 0 - 50 μA alalisvoolu
mõõtja järjestikku leegisondiga. Kui ampermeeter näitab
negatiivset tulemit, vahetage mõõtotsad ringi.
ALGUS
Ühendage alalisvoolu
ampermeeter järjestikku
leegisondiga.
Ei
Jah
Kas leek on olemas ja
ja leegivool vähemalt 1 μA
(alalisvool)?
Rikke leidmiseks vt
peatükki 14.1.
Kas leegi sondis on vool,
kuid leeki ei teki?
Kas ühendusjuhe on vigane?
Kas leegisond on vigane või
puutub vastu maandatud osi?
Jah
Jah
Jah
Jah
Ei
Ei
Ei
Ei
Remontige või asendage
vastavalt vajadusele.
Juhtblokk on vigane.
Asendage õigetüübilisega.
Kas põleti sisseviigu gaasirõhk
on õige? Kas faasi ja neutraali
polaarsus on õige? Kas
leegisondi vooluring on korras?
Kas "lukustus" toimub
samaaegselt leegi
olemasoluga?
Kütteseade toimib
VEAOTSING LÕPEB.
Probleemi püsimisel võtke
ühendust
ROBERTS GORDON
®
telefonil
Tel: +44 (0) 1902 498733
www.rg-inc.com
Remontige või asendage
vastavalt vajadusele.