Infrared Heating System Owner's Manual

ROBERTS GORDON
®
CRV-SERIES SUBMITTAL SHEET
© 2004 Roberts-Gordon
BEFORE INSTALLATIO N AND OPERATI ON OF HEATIN G EQUI PMENT, READ AND UNDERSTAND THE I NSTALLATION, O PERATION AND SERVICE MANUAL.
APPLICATIONS, ENGIN EERING AND DETAI LED GUIDANCE ON SYST EMS DESIGN, INSTALLATION AND PRODUCT PERFORMANCE IS AVAILABLE UPO N REQUEST. ROBERTS GORDON
®
PRODUCTS ARE TO BE
INSTALLED ONLY I N ACCOR DANCE WIT H LOCAL LAW S, CODES AND REGULATIONS, AND ONLY BY A CONTRACTO R QUALIFIED IN THE INST ALLATION AND SERVICE OF GAS-F IRE D HEAT ING EQUIPMEN T.
GENERAL SPECIFICATIONS
Material Specification
Reflectors
.024 Mill Finish
Aluminium (Optional - 024 Stainless
Steel Type 304).
Heater Specifications
Ignition
Fully Automatic, Three-Try, Direct Spark, Electronic
Ignition Control, 100% Safety Shut-Off.
Suspension Specifications
Hang heater with materials with a minimum working
load of 75 lbs (33 kg).
Controls Specifications
Time switches, thermostats, etc. can be wired into
the electrical supply. External controls supplied as an
option.
General Specifications for CRV-Series heaters are as follows:
Pipe Connection
1/2" NPT
(36" Stainless Steel Flex Included with Burner)
Dimensions
Vent Connection Size: 4" (10 cm) or 6" (15 cm)
Outside Air Connection Size: 4" (10 cm)
Refer to figure above for dimensional information.
Gas Inlet Pressure
Natural Gas: 4.5" w.c. Minimum 14.0" w.c. Maximum
LP Gas: 10.5" w.c. Minimum 14.0" w.c. Maximum
Electrical Rating
120V - 60 Hz., 0.3 Amp
Ignition System
Fully Automatic, Three-Try, Direct Spark, Electronic
Ignition Control, 100% Shut-Off
Reflector
Length "A"
20"
(51 cm)
10"
(24.4 cm)
6 1/2"
(16 cm)
10 3/4"
(27 cm)
4"
(10 cm)
6 7/8"
(17 cm)
3 1/2"
(9 cm)
7 5/8"
(19 cm)
14 1/4"
(36 cm)
9 1/2"
(24 cm)
5/32"
(.4 cm)
Heat Input Rate Length “A”
Recommended Minimum
Mounting Height*
Model (BTUH X1000) Minimum Maximum Spot Heating
CRV-B-2 (NG only) 20 10' (3 m) 20' (6.1 m) 8' (2.4 m)
CRV-B-4 40 12.5' (3.8 m) 25' (7.6 m) 8' (2.4 m)
CRV-B-6 60 20' (6.1 m) 35' (10.7 m) 8' (2.4 m)
CRV-B-8 80 20' (6.1 m) 45' (13.7 m) 10' (3 m)
CRV-B-9 90 25' (7.6 m) 50' (15.2 m) 10' (3 m)
CRV-B-10 100 30' (9.1 m) 60' (18.3 m) 15' (4.5 m)
CRV-B-12A (NG only) 110 35' (10.7 m) 70' (21.3 m) 15' (4.5 m)