User manual

UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL
28
SECTION 13: TROUBLESHOOTING
13.1 General
Fan and limit switch are
operating normally.
Replace temperature limit
switch.
Ensure air flow through
heat exchanger is
appropriate per the rating
plate.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Heater Operating
TROUBLESHOOT ENDS.
No
The limit switch has
tripped. See Manual Reset
Limit Switch Figure.
No
Use Troubleshooting for
Automatic Ignition Burner
Systems section to test burner.
Has burner “Locked Out”?
Ye s
No
With external controls (i.e.
thermostat) on, does the
burner continue through the
heating cycle?
No
Ye s
Does the flue blower run?
No
Use Troubleshooting for
Flue Blower section to test
fan.
Ye s
Ye s
Burner has locked out due
to ignition failure. Use
Troubleshooting for Automatic
Ignition Burner Systems
section to test burner.
Is ignition control showing a
"2 flashes" LED code?
Ye s
No
Ye s
START
Ye s
Wait 10 - 15 minutes for
limit switch to cool. Does
fan stop running?
No
Turn on supplies.
Are gas & electrical
supplies on?
Ye s
Is ignition control showing a
"4 flashes" LED code?
Ye s
No
Ye s
No
WARNING
Explosion Hazard
Installation, service and annual inspection
must be done by a contractor qualified in
the installation and service of gas-fired
heating equipment or your gas supplier.
Turn off gas and electrical supplies before
performing service or maintenance.
Failure to follow these instructions can
result in death, injury or property damage.