Installation guide
RO-MAN REVERSE OSMOSIS SYSTEM INSTALLATION GUIDE
2
PLEASE READ THIS ENTIRE GUIDE
PRIOR TO BEGINNING INSTALLATION.
T
HIS WATER SYSTEM HAS BEEN DESIGNED FOR QUICK AND SIMPLE INSTALLATION AND MAINTENANCE. BY
CAREFULLY READING THIS INSTRUCTION MANUAL AND FOLLOWING THE OPERATIONAL GUIDELINES YOU
WILL INSURE A SUCCESSFUL INSTALLATION AND RELIABLE OPERATION
. ROUTINE MAINTENANCE IS
ESSENTIAL TO THE LONGEVITY AND PERFORMANCE OF THE SYSTEM
. FILTERS SHOULD BE CHANGED
EVERY TWO TO SIX MONTHS DEPENDING ON THE QUALITY OF THE FEED WATER SUPPLY AND THE QUANTITY
OF WATER PRODUCED
.
CAUTION
DO NOT USE THIS SYSTEM WHERE THE WATER IS MICROBIOLOGICALLY UNSAFE OR OF UNKNOWN QUALITY.
CONDITIONS FOR OPERATION
TFC – Thin Film Composite
Source Water Supply – TEC
COMMUNITY/PRIVATE NON-CHLORINATED – OR CHLORINATED AS LONG AS THE
CARBON FILTER IS IN PLACE AND REPLACED EVERY
6 MONTHS
OR AFTER
RECOMMENDED GALLON THROUGHPUT,
WHICHEVER COMES FIRST
.
M
EMBRANES ARE DAMAGED BY CHLORINE.
SYSTEM PRESSURE (PRE-FILTRATION) 0-75 PSI
MEMBRANE PRESSURE RANGE 40-125 PSI
TEMPERATURE 4º-38º C (40º-100º F)
PH RANGE 3.0-13.0
MAXIMUM SUPPLY TDS LEVEL 1500 MG/L
TURBIDITY <1.0 NET TURBIDITY (NTU)
CHEMICAL PARAMETERS – TEC
HARDNESS (CACO.) <350 MG/L (<20 GPG)
IRON (FE) <0.1 MG/L
MANGANESE (MN) <0.05 MG/L
HYDROGEN SULFIDE (H2S) 0.00 MG/L
CHLORINE (CL2) 0.00 MG/L
RO-MAN.COM LTD Page 2 of 15