Datasheet

Input
PRODUCT SPECIFICATION
din rail power supply
AC/DC DIN Rail Mounted
Power Supply
PARAMETER CONDITIONS MIN TYP MAX UNITS
Input voltage
90 264
Vac
Input frequency 47 63
Input current
Full load, Vin=115Vac Full
load, Vin=230Vac
2.6
1.3
A
A
Inrush current
Cold start, Vin=115Vac Cold
start, Vin=230Vac
35
65
A
A
1. This product is built in inrush limiting circuit to protect the circuit from surge current
damages when the power is turned on. Malfunction can occur by repeating the input voltage
on and off rapidly. Therefore, sufficient interval should be given between turning on and off
the power;
2. To avoid connecting the switch or fuse to input terminal(outside of the power supply),
more consideration should be given when selecting the parts that can endure the inrush
current
Power factor(PF)
Full load, Vin=115Vac Full
load, Vin=230Vac
0.99
0.96
Stand-by power consumption Vin=230Vac 7 W
Surge voltage L-N 2
Hz
KV
Distrelec Schweiz AG, Grabenstrasse 6, 8606 Nänikon, Switzerland, T +41 44 944 99 11, info@distrelec.com, distrelec.com