Datasheet

SPECIFICATION:
Wire Code H05V2-K, H07V2-K
Cable type Stranded
Shielding unshielded
Conductor
Class 5 flexible copper conductor
Conductor insulaon
PVC (Polyvinyl Chloride) Type TI3
Packaging Sold by reel
Original Packaging
100 m
Rated voltage 600 V
Test voltage 1000 V
Standards
UL1015, BS EN 50525-2-31 BS 6231 Type CK, BS EN/IEC 60332,
BS EN 60228, UL Subj.758, CSA C22.2 No.210 (HD 21.7 S2)
Temperature range -15...+105 °C
Tri-Rated Flexible PVC Wires
SHEATH COLOURS:
Single Core, Flexible, Unshielded
Black
Light Blue
Brown
Blue
Green
Grey
Dark Blue
Green/Yellow
Orange
Pink
Red
Violet
White
Yellow
APPLICATION:
High temperature, flame retardant cable designed for use in the switch control, relay and instrumentation panels of power
switchgear
and
for
purposes
such
as
internal
connectors
in
rectifier
equipment,
motor starters and controllers. Tri-rated cable is
sometimes referred to as BS 6231 cable, H07V2-K or panel wire
Minimum bending radius
6 x Overall Diameter
Nominal Cross
Sectional Area
mm²
Maximum Diameter of
Wires in Conductor
mm
Maximum Resistance of
Conductor at 20ºC
Plain Wires
ohms/km
0.5
0.21
39
0.75
0.21
26
1
0.21
19.5
1.5
0.26
13.3
2.5
0.26
7.98
4
0.31
4.95
6
0.31
3.3
Current Rating (Peak)
A
mps
Voltage Drop
mV/A/m
11
46
14
31
17
22
21
15
30
9.1
41
5.7
53
3.8
45°C 50°C
55°C
60°C
65°C 70°C 75°C
Ambient Temperature
De-Rating Factor
1.00
0.97 0.90
0.82
0.73
0.63
0.52
DE-RATING FACTORS:
ELECTRICAL CHARASTERISTICS:
Distrelec Schweiz AG, Grabenstrasse 6, 8606 Nänikon, Switzerland, T +41 44 944 99 11, info@distrelec.com, distrelec.com

Summary of content (3 pages)