User guide

www.rletech.com 49 970.484.6510
4 Web Interface – Integration Version
All fields in the following table will not be available for each sensor. Only the configurable
options that apply to each sensor are displayed in that sensor’s configuration menu. Editable
options are as follows:
Option Description
Model To edit the sensor model, select the type of model from the drop-
down list by clicking on the down arrow to the direct right of the
sensor model field.
This number is used by the Wireless Gateway to identify what kind
of sensor is being read in to the system. The possible values are:
BAPI 76
Counter 11
SetPointOverride 5B
Thermistor 57
Wi-ASx/Wi-MS 41
Wi-DIT 61
Wi-LD 76
Wi-TC9 74
Wi-TH2 52
Wi_THS 48
Wi-TS 54
Serial Number This is the unique number broadcasted from the sensor to the
Wireless Gateway for identification. Each sensor has a unique
serial number. Enter the appropriate serial number, listed on the
bottom of the sensor, in the provided text field.
Offline Delay Users can designate how many minutes must pass before the
Wireless Gateway considers the sensor offline. Typical
transmission time is 10-20 seconds for 418MHz sensors and 3-5
minutes for 900MHz sensors.
Location/
Description
Enter a label up to 30 characters to describe the sensor and its
location.
High Temperature/
Analog Alarm
Threshold
Enter a high alarm threshold - if the value rises above this number,
an alarm is generated for this sensor.
Low Temperature/
Analog Alarm
Threshold
Enter a low alarm threshold - if the value drops below this number,
an alarm is generated for this sensor.
High Temperature
Alarm Threshold
Enter a high temperature alarm threshold - if the temperature rises
above this value, a high temperature alarm is generated.
Low Temperature
Alarm Threshold
Enter a low temperature alarm threshold - if the temperature drops
below this value, a low temperature alarm is generated.
High Humidity Alarm
Threshold
Enter a high humidity alarm threshold - if the humidity rises above
this value, a high humidity alarm is generated.
Low Humidity Alarm
Threshold
Enter a low humidity alarm threshold - if the humidity drops below
this value, a low humidity alarm is generated.
Alarm Delay The number of seconds that pass between the time the system
goes into alarm and the time that alarm is annunciated.
Table 4.2
Wireless Sensor Configuration Options