3 Web Interface – Standard Version
Editable options are as follows:
Option Description
Sensor Type ID This number is used by the Wireless Gateway to identify what kind
of sensor is being read in to the system. The possible values are:
BAPI 76
Counter 11
SetPointOverride 5B
Thermistor 57
Wi-ASx/Wi-MS 41
Wi-DIT 61
Wi-LD 76
Wi-TC9 74
Wi-TH2 52
Wi_THS 48
Wi-TS 54
Description Enter a label up to 30 characters to describe the sensor and its
location.
Serial Number This is the unique number broadcasted from the sensor to the
Wireless Gateway for identification. Each sensor has a unique
serial number. Enter the appropriate serial number, listed on the
bottom of the sensor, in the provided text field.
Offline Delay Users can designate how many minutes must pass before the
Wireless Gateway considers the sensor offline. Typical
transmission time is 10-20 seconds for 418MHz sensors and 3-5
minutes for 900MHz sensors.
Bapi / RLE Wi-LD
Radio Buttons
Bapi sensors and RLE’s Wi-LD sensor have the same sensor type
ID - 76. If this field is available in your interface, this means the
sensor you’re configuring has a sensor type ID of 76. Designate
whether this sensor is a Bapi sensor or RLE’s Wi-LD.
High Analog Alarm
Threshold
Enter a high alarm threshold - if the value rises above this number,
an alarm is generated for this sensor.
Low Analog Alarm
Threshold
Enter a low alarm threshold - if the value drops below this number,
an alarm is generated for this sensor.
High Temperature
Alarm Threshold
Enter a high temperature alarm threshold - if the temperature rises
above this value, a high temperature alarm is generated.
Low Temperature
Alarm Threshold
Enter a low temperature alarm threshold - if the temperature drops
below this value, a low temperature alarm is generated.
High Humidity Alarm
Threshold
Enter a high humidity alarm threshold - if the humidity rises above
this value, a high humidity alarm is generated.
Low Humidity Alarm
Threshold
Enter a low humidity alarm threshold - if the humidity drops below
this value, a low humidity alarm is generated.
Alarm Delay The number of seconds that pass between the time the system
goes into alarm and the time that alarm is annunciated.
High Temperature
Warning Threshold
Enter a high temperature warning threshold - if the temperature
rises above this value, a high temperature warning is generated.
Table 3.15
Sensors Tab Configuration Options