User guide
www.rletech.com 13 970.484.6510
C HAPTER
CHAP TER 0GETTING STARTED
2.1. Installation
The Wireless Gateway comes with two brackets that, when attached to the device, allow it to
be mounted in a 19-inch rack. Remove the screws from the side of the device, put the brackets
in place, and reapply the screws. Mount the device in a rack. Use the proper anchoring method
to mount the unit securely.
2.2. Wiring
2.2.1 Power Supply and Ground Connections
RLE Technologies recommends powering the Wireless Gateway from a UPS supply so the
device can send alarm notifications during a power outage. Connect an 18AWG ground wire
from the ground terminal to a suitable earth ground. Plug the wall adapter into P1 and a UPS
outlet. The wall adapter has a five foot (1.524m) power cord.
Connect 24VDC to the unit through either the jack input or terminal block.
MOUNTING BRACKETS