User Manual

PT2E-1140
4−6 Alarm (Transmission) Test Method
Alarm functions can be confirmed.
When make alarm test (transmission test), announce it to respective
department beforehand. Carry it out after making proper treatment.
CAUTION
Press SET switch in menu display .
Press UP switch or DOWN switch to select whether alarm contact is
activated or not.
(No operation)⇔ (Operation)
Press SET switch● to decide.
When alarm test mode is entered, test level (zero value) is flickered on LCD
display .
When “ON” is selected at this time, ZERO light and SPAN light are flickering
simultaneously.
To press UP switch▲ or DOWN switch▼, test level(between 0 to full scale, over
scale) can be changed.( 4-20mA output is also changed according to indication).
Test level exceeds 1
st
alarm point, 1
st
alarm is activated.
(After alarm delay time passed, AL1 light is lighting, and 1
st
alarm contact is activated
if “ON” is chosen).
Test level exceeds 2
nd
alarm point, 2
nd
alarm is activated.
(After alarm delay time passed, AL2 light is lighting, and 2
nd
alarm contact is activated
if ”ON” is chosen).
24