7 Maintenance 7-2. Regular maintenance mode
- 57 - RM-5000
<Environmental Setting 1 "2-5">
In the environmental setting 1, specify the operation setting.
<<Environmental Setting 1>>
During maintenance
During inhibit
Lamp on
Lamp off
Lamp blinking
2-5. SETTING1
Press SET key.
SE 0. INHIBIT
Set Inhibit.
Press the or key to select
either ON/OFF, and then press the
SET key to confirm the selection.
When ON is selected, the
character I is displayed on the
LCD. As a result, an alarm is not
triggered to external circuits even
though the indicator/alarm unit is
in the detection mode.
SE 1. ALM P
Set the alarm setpoint value.
A
larm setpoint value setting
=> P58
SE 2. ALM DLY
Set the alarm delay time.
Press the or key to
change the value (second),
and then press the SET key
to confirm the value.
SE 3. F TEST
Perform a fault alarm test.
Fault Alarm Test
=> P58
To SE 0.INHIBIT Setting