Instruction Manual

6 Operations and Functions 6-2. Fault alarm activation
- 47 - RM-5000
<Response to Gas Alarm>
In case of responding to a leaked gas
When a gas alarm is triggered, take actions in accordance with your management rules of gas alarm.
Normally, take the following actions.
Check the reading of the indicator/alarm unit.
NOTE
If a gas leak is momentary, the reading may already have dropped when you check it. In addition, when
the alarm is triggered by noise or other incidental conditions other than a gas, the reading may have
already dropped.
Based on your management rules of gas alarm, no one should be allowed to access the monitored zone
to ensure safety.
If the Gas Concentration Display continues to be shown, close the main valve of the gas, and then check
that the gas concentration reading is dropped.
Assuming that gases remain, wear protective equipment to avoid dangers and go to the gas leak point,
and then check if gases remain using a portable gas detector etc.
If you can determine that the point is free from dangers, take actions to fix the gas leak.
6-2. Fault alarm activation
A fault alarm is triggered when the indicator/alarm unit detects abnormalities <<Auto-Reset>>.
After a fault alarm is triggered, the FAULT lamp (yellow) blinks and an error message is displayed on the
LCD. Determine the causes and take appropriate actions.
After the indicator/alarm unit is successfully returned from the fault, it restarts with the process normally
performed right after it is turned on (initial clear).
If the indicator/alarm unit has problems and is repeatedly malfunctioning, contact RIKEN KEIKI immediately.
* Display example: E-1 DETECTOR
sensor abnormality
NOTE
For information on malfunctions (error messages), see "9. Troubleshooting".