Instruction Manual

5 How to Operate 5-8. How to exit
RM-5000 - 42 -
5-8. How to exit
To turn off the indicator/alarm unit, open the front cover of the main unit, and turn "OFF" the power switch.
Then, turn off the power supply (24 VDC) to the indicator/alarm unit.
WARNING
When the indicator/alarm unit is turned off, an alarm may be activated on the upper (central)
system.
Before turning off the indicator/alarm unit, the inhibit (point skip) on the upper (central) system
must be activated.
Decide whether the power can be turned off by checking the operation of the devices connected
to the external output or external contact output terminal of the indicator/alarm unit.
If the alarm contact is energized (option), it is activated when the indicator/alarm unit is turned
“OFF”.