Instruction Manual

4 How to Use 4-5. How to wire
- 21 - RM-5000
4-5. How to wire
<Recommended Cables>
Model Cable specifications
GP-5001
NC-5001
NC-5001W
SP-5001
Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVV (1.25 sq or 2.0 sq) - 4-core or 6-core
Signal: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact: Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
NP-5001 Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 4-core or 6-core
Signal: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact: Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
OX-5001
OX-5002
RM-5002
Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Signal: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact: Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
GH-5001 Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 3-core or 5-core
Signal: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact: Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
EC-5002 Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core or 4-core
Signal: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact: Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
RM-5003 Power supply: Equivalent to CVV (1.25 sq or 2.0 sq) - 2-core
Detector head: Equivalent to CVVS (1.25 sq or 2.0 sq) - 3-core
Signal: Equivalent to CVVS (1.25 sq or 2.0 sq) - 2-core
Contact: Equivalent to CVV (1.25 sq or 2.0 sq) - max. 6-core
CAUTION
Use the specified cables for each of the connections between the indicator/alarm unit and the
detector head.
When wiring, be careful not to apply stresses on the terminal plate when (overweight) cables are
installed.
The power cables and signal cables must not be installed together with the motor power cables,
etc.
When stranded wires are used, prevent wires from contacting each other.
Use the specified tools to wire.