Oxygen Transmitter • 22 Pioneer Operator’s Manual (PRELIMINARY)
10. Reconnect the wiring from the Pioneer to the interconnect terminal strip as shown in
Table 3 and Figure 3, Wiring the Oxygen Transmitter to the Pioneer Gas Monitor.
11. Reconnect the wiring from the (2-point) sensor terminal block in the detector junction
box to the ampliers detector terminal strip as shown in Table 4 and Figure 3, Wiring
the Oxygen Transmitter to the Pioneer Gas Monitor.
12. Place the Pioneers power switch in the ON position.
13. Calibrate the oxygen transmitter as described in the Calibration section of this insert.
Table 3: Reconnecting the Oxygen Amplier to the Pioneer Gas Monitor
Amplier
Interconnect Terminal Strip
Pioneer Analyzer Card
4/20 FB 4-20 (Terminal 5)
24V + 24 V (Terminal 6)
Table 4: Reconnecting the Oxygen Detector to the Amplier
Sensor
Terminal Block
Amplier
Interconnect Terminal Strip
+ (white) OXY W
(green) OXY G