Manual
5 M2 Transmitter Operator’s Manual
Magnetic Wand
The magnetic wand is a short plastic rod with a magnet in one end. It is used to actuate
the magnetic control switches on the control PCB while the junction box cover is still
installed so that non-intrusive calibration can be performed.
Gas Detector
The gas detector senses the target gas and is mounted in a 3/4” conduit hub on the right
bottom side of the M2. A variety of detectors may be used with the M2. Table 2 below lists
the detectors that can be used with the M2.
Table 2: M2 Detectors
Target Gas, Range Detector(s) Used
Combustible Gas, 0 - 100% LEL • 61-0140RK (Catalytic UL version)
• 61-0140RK-05 (Catalytic CSA version)
Hydrogen, 0 - 100% LEL • NC-6205-01 (Catalytic UL version, hydrogen specific)
• NC-6205-05 (Catalytic CSA version, hydrogen specific)
CH
4
, 0 - 100% LEL • 61-0190RK-CH4 (IR UL)
HC, 0 - 100% LEL (cal. to propane) • 61-0190RK-HC (IR UL)
CH
4
, 0 - 100% volume • 61-0192RK-CH4 (IR UL)
CO
2
, 0 - 5,000 ppm • 61-0191RK-02 (IR UL)
• 61-0198RK-02 (IR)
CO
2
, 0 - 5% • 61-0191RK-03 (IR UL)
• 61-0198RK-03 (IR)
CO
2
, 0 - 50% • 61-0191RK-05 (IR UL)
• 61-0198RK-05 (IR)
CO
2
, 0 - 100% • 61-0191RK-10 (IR UL)
• 61-0198RK-10 (IR)
Oxygen, 0 - 25% • 65-2494RK (capillary)
• 65-2510RK (partial pressure)
• 65-2511RK (capillary)
• 65-2514RK (capillary, CSA)
CO, 0 - 300 ppm • 65-2433RK-05 (CSA)
• 65-2496RK
H
2
S, 0 - 100 ppm • 65-2423RK-05 (CSA)
• 65-2495RK
NH
3
, 0 - 75 ppm • 65-2300RK-NH3
AsH
3
, 0 - 1.5 ppm • 65-2300RK-ASH3
Cl
2
, 0 - 3 ppm • 65-2300RK-CL2
Cl
2
, 0 - 10 ppm • 65-2300RK-CL-10
PH
3
, 0 - 1 ppm • 65-2300RK-PH3