Owner's manual

45 M2 Rig Monitor Operator’s Manual
Appendix A: Control Button Quick Reference Guide
The M2 Rig Monitor’s control buttons allow access to operational modes, resetting of
alarms, and display of the Information Screen. Table 12 shows which button combinations
perform these functions and which parameters are available for adjustment while in the
operational modes. While in these modes, display prompts showing a “?” require you to
respond by pressing either the UP/YES (for yes) or DOWN/NO (for no) button. To
change parameter settings, use the UP/YES and DOWN/NO buttons to get the desired
setting, then press and release the ENTER button to accept the setting.
Table 12: Control Button Quick Reference Chart
Mode Entered or
Function Performed
Button
Combination
Adjustable or Viewable Parameters
Alarm Reset Press and
Release ENTER
n/a
Show Information
Screen
Press and Hold
DOWN/NO
•Input Voltage
M2 Rig Monitor Version/Revision
Information
Calibration Mode Press and Hold
UP/YES for 5
seconds
Fresh Air Adjust
Span (or Zero for Oxygen) Adjust with
Calibration Gas
Configuration Mode Press and Hold
UP/YES &
ENTER for 5
seconds
Alarm Levels
Increasing or Decreasing Alarms
Normally Energized or Normally De-
energized Relays
Latching or Self-resetting Alarms
Alarm On Delay
Alarm Off Delay (if self-resetting)
Zero Suppression
Noise Filter
Calibration Time-out Period
Gas Type Mode Press and Hold
UP/YES and
DOWN/NO for
5 seconds
Gas Type
Modbus Mode Press and Hold
DOWN/NO and
ENTER for 5
seconds
Enable or Disable Modbus
•Slave ID
•Baud Rate
•Parity
Response Delay