Instruction Manual

PT2E-1052
19
+24V
GND
Sig
4−6−4.
Terminal plate
45 789101112
4−7.Example of cable connection
4−7−1.Connection with indicator/alarm unit
(EC-583, EC-573A): (3-wire type)
Short circuit
4−7−2.
Connection with indicator unit, DCS, PLC
(4-wire type)
Trouble contact
ALM2 contact
ALM1 contact
4∼20mA
+ ― +
EC-583
EC-573A
DC24V
NOTE
Terminals 4 & 5 are
not in use.
2
3
4
5
E
GD-K71D
Detector
E
1
2
3
4
56
E
E
DC24V
(+) (-)
GND
Sig
Indicator(RM-582,etc.)
Upper system(DCS, PLC)
GD-K71D
Detector
16
NOTE
In case of 4-wire type, power supply unit(DC24V) is required separately.