Manual

7 Regular Maintenance Mode
- 61 - GD-70D
<Energized/De-Energized Contact Setting "2-10" - "SET 6">
Energized/De-Energized Contact Setting
PW A1 A2 F LCD
SET 6. RLY PTRN
Press the SET key.
SET 6
RLY PTRN
MAINTENANCE
nd
AL1 RLY
MAINTENANCE
/
nE
AL1 RLY
MAINTENANCE
First Alarm Contact
Setting
Select either
nd(De-Energized)/nE(Energi
zed), and then press the
SET key to confirm the
selection. (Press the MODE
key to skip this menu.)
nd
AL2 RLY
MAINTENANCE
/
nE
AL2 RLY
MAINTENANCE
Second Alarm Contact
Setting
Select either nd
(De-Energized)/nE
(Energized), and then press
the SET key to confirm the
selection. (Press the MODE
key to skip this menu.)
nd
FLT RLY
MAINTENANCE
/
nE
FLT RLY
MAINTENANCE
Fault Alarm Contact
Setting
Select either nd
(De-Energized)/nE
(Energized), and then press
the SET key to confirm the
selection. (Press the MODE
key to skip this menu.)
Return to
SET 6. RLY PTRN
NOTE
When De-energized is selected, the relay is energized and activated in response to an alarm (de-energized
at a normal environment).
When the contact "a" is used, it is open at a normal environment while closed in response to an alarm.
When the contact "b" is used, it is activated conversely.
When Energized is selected, the relay is energized at a normal environment (de-energized in response to
an alarm).
When the contact "a" is used, it is closed at a normal environment while open in response to an alarm.
In addition, it is closed when the power is OFF.
When the contact "b" is used, it is activated conversely.