7 Regular Maintenance Mode
- 53 - GD-70D
<Environmental Setting 1 "2-9">
In the environmental setting 1, specify the operation setting.
Environmental Setting 1
PW A1 A2 F LCD
2-9.SETTING1
Press the SET key.
2- 9
SETTING1
MAINTENANCE
SET 0
INHIBIT
MAINTENANCE
SET
OFF
INHIBIT
MAINTENANCE
↓↑
ON
INHIBIT
MAINTENANCE
INHIBIT
SET 0.INHIBIT
Set the inhibit.
Select either ON/OFF, and
then press the SET key to
confirm the selection.
When ON is selected, the
message INHIBIT is
displayed on the LCD. As a
result, an alarm is not
triggered to external circuits
even though the detector is in
the detection mode.
|
| |
|
SET 1
ALM P
MAINTENANCE
SET
Alarm Value Setting
P54
SET 1.ALM P
Set the alarm value.
SET 2
ALM DLY
MAINTENANCE
SET
2
ALM DLY
MAINTENANCE
SET 2.ALM DLY
Set the alarm delay time.
Select the number (second)
by pressing the or key,
and then press the SET key to
confirm the value.
SET 3
MAINTE
MAINTENANCE
SET
-----
MAINTE
MAINTENANCE
SET 3. MAINTE
This is used to stop only the
pump for replacing the pump
or for another purpose.
Press the SET key to stop the
pump. Press the SET key
again to restart the pump,
which returns to the original
state. (You can also press the
MODE key to cancel this
menu and restart the pump.)
|
| |
|
Pump Stop
(Drive Sound Stop)
SET 4
F TEST
MAINTENANCE
SET
Fault Alarm Test
P54
SET 4.F TEST
Perform a fault alarm test.
To
SET 0.INHIBIT Setting