User Manual

13 Operation GasWatch 2 Operator’s Manual
Alarms
This section covers alarm indications. It also tells you how to reset the
GasWatch 2 after an alarm has occurred and how to respond to an alarm
condition.
Alarm Indications, GW-2C & GW-2H
The GW-2C and the GW-2H will sound an alarm and the unit will vibrate
when the target gas concentration, CO or H
2
S, rises above the low alarm
point. The GasWatch 2 also sounds an alarm and vibrates when the high
alarm point, the STEL alarm point, or the TWA alarm point is reached. It
also has a low battery warning, a dead battery alarm, an over range alarm,
a sensor failure alarm, and a system failure alarm. See Table 3 below for a
description of each alarm indication.
Alarm Indications, GW-2X
The GW-2X will sound an alarm and the unit will vibrate when the oxygen
concentration falls below the low alarm point or rises above the high alarm
point. It also has a low battery warning, a dead battery alarm, an over
range alarm, a sensor failure alarm, and a system failure alarm. See
Table 3 below for a description of each alarm indication.
The table below summarizes the types of alarms produced by the
GasWatch 2.
Table 3: Alarm Types and Indications
Alarm Type LCD Indications Other Indications
Low Alarm
Concentration of gas
rises above the low
alarm point, or for the
GW-2X, falls below
the low alarm point.
Gas reading
flashes.
Back light turns on.
Pulsing tone once
per second.
Unit vibrates once
per second.
Alarm lights flash
once per second.
High Alarm
Concentration of gas
rises above the high
alarm point.
Gas reading
flashes.
Back light turns on.
Pulsing tone twice
per second.
Unit vibrates twice
per second.
Alarm light flashes
twice per second.