Manual

Gas Tracer Operator’s Manual Using Maintenance Mode 153
1. Use the AIR or (SHIFT) buttons to display the ALARM--P
menu item. Press and release the POWER ENTER button.
2. You may then select a channel. Use the AIR or (SHIFT) buttons
to select a channel. The combustible gas channel is shown for
example.
3. Press the POWER ENTER button to display the warning setting for
the combustible channel. It will be flashing.
4. Use the AIR or (SHIFT) buttons to change the warning setting.
5. Press POWER ENTER to save the setting. The alarm setting for the
combustible gas channel will then be displayed.
6. Use the AIR or (SHIFT) buttons to change the alarm setting.
- - -
%LEL
MAINTENANCE
CH4
ALARM--P
10
%LEL
MAINTENANCE
CH4
WARNING
50
%LEL
MAINTENANCE
CH4
ALARM