Manual

Digester Gas Monitor Operator’s Manual Alarm Indications 41
NOTE: You can set the channel alarm relays to be either all normally energized or all
normally de-energized in the Global Menu. The following sections describe the
factory settings of normally de-energized for the channel relays. The fail relay is
factory-set as normally energized and is not user adjustable. See “Viewing and
Changing Global Parameters” on page 47 for instructions to change the channel
alarm relays.
Alarm 1 Condition
This section describes the indications for an alarm 1 condition and suggests responses to
an alarm 1 condition.
Alarm 1 Condition Indications
When the gas reading of an active channel reaches the alarm 1 setpoint, the Digester Gas
Monitor senses an alarm 1 condition. The Digester Gas Monitor alerts you to an alarm 1
condition as follows:
the alarm 1 LED turns on
the gas reading in alarm 1 condition alternates with the ALARM-1 message
the buzzer sounds a pulsing tone
the applicable alarm 1 channel relay energizes
if installed and set to activate in an alarm 1 condition, the horn/strobe flashes and
sounds a pulsing tone
NOTE: The oxygen alarm 1 condition has a 30 second factory set delay. The delay may
be changed in the Configuration Menu.
Fail Disconnected or
misconnected
detector wiring
Display reading below
-10% of full scale or
lower
Malfunctioning
components
Fail LED is on
FAIL message replaces the
gas reading
If installed and set to activate
for fail, horn/strobe flashes
NOTE: There is a 30 second delay
on the fail indications.
Buzzer sounds a
steady tone
If installed and set to
activate for a fail
condition, the horn/
strobe sounds a
pulsing tone
Flow Fail Flow to system falls
below 1.6 SCFH
Display alternates between
FLOW FAIL and normal
screen
If installed, the horn/strobe
activates
A 60 second fresh air purge is
initialized
Flow through system will be
stopped
Buzzer sounds a
steady tone
If installed, the horn/
strobe sounds a
pulsing tone
Low
Battery
No AC power and DC
power source (primary or
backup) less than 18.5
volts.
FAIL LED is on
Display shows LOW POWER
STANDBY message and the
input DC voltage
None
Table 6: Visual and Audible Alarm Indications
Condition Cause Visual Indication(s) Audible Indication