Owner's manual

22 Beacon 110 Operator’s Manual
Alarm Indications
NOTE: The Beacon 110 includes alarm on and alarm off delay settings for alarm 1 and
alarm 2. The alarm indications described in this section operate according to
the factory set alarm settings. See Table 7 on page 27 for all the factory
settings.
NOTE: You can select normally energized (N. EN) or normally de-energized (N. DE-
EN) alarm 1 and alarm 2 relay settings in Configuration Mode. The following
sections describe the standard factory setting for these relays which is
N. DE-EN.
The fail relay is set as normally energized in the firmware and is not user-
adjustable.
Table 6: Visual and Audible Alarm Indications
Condition Cause Visual Indication(s)
Audible
Indication
Alarm 1
1
Increasing (decreasing for O
2
) gas read-
ing at or above the alarm 1 setpoint
Alarm 1 LED is on
Gas reading alternates with
ALARM-1 message
If installed and set to
activate for alarm 1, strobe
flashes
Pulsing tone
Alarm 2
1
Increasing gas reading at or above the
alarm 2 setpoint
Alarm 2 LED is on
Gas reading alternates with
ALARM-2 message
If installed and set to
activate for alarm 2, strobe
flashes
Pulsing tone
Fail Disconnected or misconnected
detector head wiring
Display reading at -10% of full scale
or lower
Defective components
Fail LED is on
FAIL message replaces
gas reading
If installed, strobe flashes
Steady tone
Low Power DC power source less than 18.5 volts. Fail LED is on
LowPower message and
actual voltage of incoming
DC power
None
*
1
If the Beacon 110 is in both an alarm 1 and an alarm 2 condition, both alarm LEDs
are on and the display alternates between the gas reading and the ALMS 1&2 message.