User Manual

5 1 65-2649RK-HC-04 M2A Transmitter Operator’s Manual
1=Self-Resetting
Register 11
Register 11 is the alarm 2 ON delay.
Integer value is in seconds.
Register 12
Register 12 is the alarm 2 O FF d e lay.
Integer value is in seconds.
Register 13
Register 13 is the zero suppression.
To xics and LEL: 0%-6% Full Scale
Oxygen: 0%-0.7% Oxygen
Value must be an integer. Any decimals are omitted.
Register 14
Register 14 is the noise filter.
Integer value is in seconds (0-60 in 5 second increments).
Register 15
Register 15 is the calibration timeout.
Va lue is in minutes (5, 10, 15, 20, 25, or 30).
Register 16
Register 16 is explained in “Supported Modbus Func tions” in the M2 A manual.
Register 17
Register 17 is the calibration month (MSB) and day (LSB).
This is zero-based (e.g. January=0 and the 1st=0).
Register 18
Register 18 is the calibra tion year.