4 5 65-2649RK-HC-04 M2A Transmitter Operator’s Manual
Function Code 16: Write Registers
There are 21 registers in Function Code 16 that can be used to write to the M2A. This
manual only describes Register 16 because it can be used to reset an alarm cond ition. For a
complete description of Func tion Cod e 16, request Appendix C from RKI Instrument s,
Inc.
Register 16
Register 16 performs the same function as the ENTER button on the M2A. It is useful for
remotely silencing alarms. With the M2A in an alarm condition , bit [0] can b e used to
silence it.
Table 12: Register 16, Button Function
NOTE: Register 40 in Function Code 03, the remo te configuration register, must be set
to 1 in order for Register 16 to work.
Bit Value & Field
[0] ENTER (used for “Alarm Reset”)
0=Not Pressed
1=Pressed