Owner's manual
65-2397RK CO
2
Transmitter • 1
Overview
This manual describes the 65-2397RK CO
2
transmitter. This manual also describes how to
install, start up, configure, maintain, and calibrate the transmitter when it is used with a
gas monitoring controller. A parts list at the end of this manual lists replacement parts and
accessories for the CO
2
transmitter.
Specifications
Table 1 lists specifications for the CO
2
transmitter.
WARNING: When using the 65-2397RK, you must follow the instructions and warnings
in this manual to assure proper and safe operation of the 65-2397RK and to
minimize the risk of personal injury. Be sure to maintain and periodically
calibrate the 65-2397RK as described in this manual.
Table 1:Specifications
Description Specification
Target Gas Carbon Dioxide (CO
2
)
Sampling Method Diffusion
Signal Output 4 to 20 mA
Detection Range 65-2397RK-02: 0-5,000 ppm
65-2397RK-03: 0-5% Volume
65-2397RK-05: 0-50% Volume
65-2397RK-10: 0-100% Volume
Response Time 90% in 45 seconds
Operating Temperature
-4°F to 122°F (-20°C to 50°C)
Accuracy ± 5% of reading or ± 2% of full scale (whichever is greater)