65-2395RK-CH4 Methane Transmitter • 1
Overview
This manual describes the 65-2395RK-CH4 methane transmitter. This manual also
describes how to install, start up, configure, maintain, and calibrate the transmitter when
it is used with a gas monitoring controller. A parts list at the end of this manual lists
replacement parts and accessories for the methane transmitter.
Specifications
Table 1 lists specifications for the methane transmitter.
WARNING: When using the 65-2395RK-CH4, you must follow the instructions and
warnings in this manual to assure proper and safe operation of the
65-2395RK-CH4 and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 65-2395RK-CH4 as described in
this manual.
Table 1:Specifications
Description Specification
Target Gas Methane (CH
4
)
Area Classification Explosionproof for Class I, Groups B, C, and D
Sampling Method Diffusion
Signal Output 4 to 20 mA
Detection Range 0 to 100% volume
Response Time 90% in 45 seconds
Operating Temperature
-4°F to 122°F (-20°C to 50°C)
Accuracy ± 5% of reading or ± 2% of full scale (whichever is greater)