Instruction Manual

65-2330RK H
2
S Transmitter • 7
11. Connect the wires to the applicable detector/transmitter terminal strip at the
controller as shown in Figure 4.
Figure 4: Wiring the H
2
S Transmitter to a Controller
12. If shielded cable is used, connect the cable’s drain wire to an available chassis (earth)
ground at the controller. RKI controllers typically have a ground stud that can be used
to ground the cable’s drain wire.
Start Up
This section describes procedures to start up the H
2
S transmitter and place the transmitter
into normal operation.
Introducing Incoming Power
1. Complete the installation procedures described earlier in this manual.
2. Verify that the power wiring to the controller is correct and secure. Refer to the
controller operator’s manual.
3. Turn on power to the controller.
4. Turn on the controller.
S
SIG/PWR
ZERO
SPAN
Black
Red
Controller
4 - 20 mA In (S)
+ 24 VDC
Cable Shield
TOXIC OXY
J-Box
H2S Detector