6 • 35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector
Installation
This section describes procedures to mount the sample-draw detector in the monitoring
environment and wire the sample-draw detector to a controller.
Mounting the Sample-Draw Detector
1. Select the mounting site. Consider the following when you select the mounting site:
• Is there enough room to open the housing door and make wiring and tubing connections at
the bottom of the housing?
• Make sure there is sufficient room to perform start-up, maintenance, and calibration
procedures.
• Are the flowmeter and status LEDs visible?
Figure 3: Outline and Mounting Dimensions
Ø.30x.50(4X)MOUNTING
.78
1.13
.40
Pilot Fail
.85
.80
4.50
NOTE: Housing is4.3 inches deep
8.88
4.00
6.50
35-3001
www.rkiinstruments.com
Sampl e Drawing
Gas Detector
8.50