Owner's manual
10 • 35-3001-01H Hydrogen Sample-Draw Detector
8. Connect the wires to the applicable detector/transmitter terminal strip at the controller as
shown in Figure 5. Refer to the controller operator’s manual and the controller detector head
specification sheet for the 35-3001-01H for detector/terminal strip connections specific to the
controller.
Figure 5: Wiring the Sample-Draw Detector to a Controller
9. If shielded cable is used, connect the cable’s drain wire to an available chassis (earth) ground at
the controller. RKI controllers typically have a ground stud that can be used to ground the
cable’s drain wire.
Gree
n
Black
Red
Whit
e
Not Used on
This Version
LEL/IR
PATS101PATS101PATS201PATS201
AMP 2 LEL/IR
OXY
OXY
AMP 1
AMP 1
AMP 2
Red
Green
Black
White
+24VDC
Controller D etector/
Transmitter Terminal
Strip Terminals
Controller Detector/
Transmitter Terminal
Strip, LEL D etector
Terminals
- (DC Ground)
To
Hydrogen
Sensor