Owner's manual

4 • Sample Draw Combustible Gas Detector
Status lights
Two status lights are above the owmeter. They are also visible through the window in
the housing door.
Pilot light
The green Pilot light is on when the sample draw detector is receiving power.
Fail light
The red Fail light is on when the sample ow rate is below the low ow level.
NOTE:
The default low ow level is 0.6 SCFH (
±
0.2). See “Adjusting the Low Flow
Setting” on page 15 to adjust this setting.
Pressure switch
The pressure switch is mounted to the opposite side of the main circuit board. The
pressure switch monitors the ow rate of the incoming gas sample.
If the ow rate falls below the preset low ow level, the pressure switch causes the fail
relay to interrupt the signal in the 4-20 mA line. This causes a downscale reading at the
monitor. The low ow level is factory-set at 0.6 SCFH (
±
0.2 SCFH).
EXHAUST fitting
The EXHAUST tting on the right side of the housing allows the gas sample to exit the
sample draw detector. The EXHAUST tting accepts 1/4 in. rigid tubing. See the
Installation section on page 7 to connect tubing to the EXHAUST tting.
Detection System
The detection system consists of the combustible gas sensor, the hydrogen transmitter,
and the main circuit board.
Combustible gas sensor
The combustible gas sensor is installed in a cavity block. The cavity block is mounted to
the aluminum
subpanel near the bottom of the sample draw detector. The combustible
gas sensor includes the sensing elements, ame arrestor, connector, and sensor leads.
NOTE:
The cavity block includes a cavity for an oxygen sensor. This version of the
sample draw detector does not include the oxygen sensor.
Sensing elements
Two sensing elements are protected within the sensor assembly. Through a series of
thermal and electronic reactions, these elements produce an output that is proportional to
the detection range of the sample draw detector. The transmitter converts the output to a 4
- 20 mA signal which can be used by a recording or monitoring device.
The porous ame arrestor allows the gas sample to enter the sensor assembly and contact
the sensing element. The ame arrestor also contains sparks within the sensor.