User guide

Model 1017-04 Operator’s Manual • 1
Sample-Draw Combustible Gas Detection
Overview
This manual describes the Model 1017-04 sample draw combustible gas detector. This
manual also describes how to install, start up, maintain, and calibrate the Model 1017-04.
A parts list at the end of this manual lists replacement parts and accessories.
Specifications
Table 1 lists specifications for the Model 1017-04.
WARNING: When using the Model 1017-04, you must follow the instructions and
warnings in this manual to assure proper and safe operation of the Model
1017-04 and to minimize the risk of personal injury. Be sure to maintain
and periodically calibrate the Model 1017-04 as described in this manual.
Table 1: Specifications
Target Gas Combustible gas, methane calibration standard
Input Power 24 VDC
Construction (housing) Cast Aluminum Alloy, Explosion Proof for Class I,
Groups B, C, & D
Dimensions 7.00 in. H x 7.00 in.W x 6.13 in. D
Sampling Method Sample-draw
Recommended Sample Flow 2.0 SCFH
Detection Range 0 - 100% LEL/0 - 10% LEL
0 - 100% LEL/0 - 2000 ppm
Response Time 90% in 30 seconds
Accuracy ±5% of reading or ± 2% LEL (whichever is greater)