Owner's manual

Model 1017-01 Operator’s Manual • 1
Sample-Draw Combustible Gas Detection
Overview
This manual describes the Model 1017-01 sample draw combustible gas detector. This
manual also describes how to install, start up, maintain, and calibrate the Model 1017-01.
A parts list at the end of this manual lists replacement parts and accessories.
Specifications
Table 1 lists specifications for the Model 1017-01.
WARNING: When using the Model 1017-01, you must follow the instructions and
warnings in this manual to assure proper and safe operation of the Model
1017-01 and to minimize the risk of personal injury. Be sure to maintain
and periodically calibrate the Model 1017-01 as described in this manual.
Table 1: Specifications
Target Gas Combustible gas, methane calibration standard
Input Power 24 VDC
Construction (housing) Cast Aluminum Alloy, Explosion Proof for Class I,
Groups B, C, & D
Dimensions 7.00 in. H x 7.00 in.W x 6.13 in. D
Sampling Method Sample-draw
Recommended Sample Flow 1.0 LPM
Detection Range 0 to 100% LEL
Response Time 90% in 30 seconds
Accuracy ±5% of reading or ± 2% LEL (whichever is greater)