Specifications
4. CONNECTION TO FUJI PLC
4.2 Serial connection
4 - 15
4
CONNECTION TO FUJI PLC
4.2.6 GOT Side Settings
Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
1. Select [Common] [Controller Setting] from the
menu.
2. The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3. Set the following items.
• Manufacturer: FUJI
• Controller Type: Set either of the following
• FUJI MICREX-F Series
• FUJI MICREX-SX SPH
• I/F: Interface to be used
• Driver: Set either of the following.
• FUJI MICREX-F Series
• FUJI MICREX-SX SPH
4. The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
■ Communication detail settings
Click the [OK] button when settings are completed.
POINTPOINTPOINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
Communication detail settings
Make the settings according to the usage environment.
(For FUJI MICREX-F)
2.
3.
4.
Click!
Item Description Range
Transmission
Speed
Set this item when change the
transmission speed used for
communication with the connected
equipment. (Default: 9600bps)
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
Data Bit
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bits)
7bits/8bits
Stop Bit
Specify the stop bit length for
communications. (Default: 1bit)
1bit/2bits
Parity
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: Even)
None
Even
Odd
Retry
Set the number of retries to be
performed when a communication
error occurs. (Default: 0time)
0 to 5times
Timeout Time
Set the time period for a
communication to time out.
(Default: 3sec)
1 to 30sec
Host Address
Specify the host address (station No.
of the GOT to which the PLC is
connected) in the connected network.
(Default: 0)
0 to 99
Delay Time
Set this item to adjust the
transmission timing of the
communication request from the
GOT. (Default: 5ms)
0 to 300ms