Specifications

15 - 14
15. CONNECTION TO SIEMENS PLC
15.3 Ethernet Connection
(2) Ethernet connection type: OP communication
This section describes the Ethernet setting for the
communication driver SIEMENS OP (Ethernet).
*1 Connection No./Rack No. and Module Position/Slot No. are
unnecessary for S7-1200 OP.
*2 Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
Communication detail settings
IP Filter Setting
To improve security, the GOT 2000 series supports the
IP Filter Setting.
For details on the IP Filter Setting, refer to the following
manual.
GT Designer3 (GOT2000) Help
Item Description Set value
Host
The host is displayed. (The host is
indicated with an asterisk (*).)
Net No.
Set the network No. of the
connected Ethernet module.
(Default: blank)
1 to 239
Station
*2
Set the station No. of the connected
Ethernet module.
(Default: blank)
1 to 254
Type Set the PLC type to be connected.
S7-200 OP
S7-300/400 OP
S7-1200 OP
IP Address
Set the IP address of the connected
Ethernet module.
(Default: blank)
PLC side IP
address
Port No. 102 (fixed) 102 (fixed)
Connection
No./Rack No.
*1
Set the Connection No./Rack No. set
on the PLC side.
(Default: 0)
0 to 7
Module
Position/Slot
No.
*1
Set the Module Position/Slot No. set
on the PLC side.
(Default)
S7-200 OP: 0
S7-300/400 OP: 2
S7-200
OP: 0 to 6
S7-300/400
OP: 0 to 31
Communication TCP (fixed) TCP (fixed)