15. CONNECTION TO SIEMENS PLC
15.3 Ethernet Connection
15 - 13
CONNECTION TO SIEMENS PLC
15
GOT Ethernet setting Ethernet setting
(1) Ethernet connection type: FETCH/WRITE
This section describes the Ethernet setting for the
communication driver SIEMENS S7 (Ethernet).
*1 Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
Communication detail settings
Item Description Range
GOT IP Address
Set the IP address of the GOT.
(Default: 192.168.0.18)
0.0.0.0 to
255.255.255.255
Subnet Mask
Set the subnet mask for the sub
network. (Only for connection via
router)
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
0.0.0.0 to
255.255.255.255
Default
Gateway
Set the router address of the default
gateway where the GOT is
connected. (Only for connection via
router)
(Default: 0.0.0.0)
0.0.0.0 to
255.255.255.255
Periphral S/W
Communication
Port No.
Set the GOT port No. for the S/W
communication.
(Default: 5015)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013, and
49153)
Transparent
Port No.
Set the GOT port No. for the
transparent function.
(Default: 5014)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013, and
49153)
Item Description Set value
Host
The host is displayed. (The host is
indicated with an asterisk (*).)
Net No.
Set the network No. of the
connected Ethernet module.
(Default: blank)
1 to 239
Station
*1
Set the station No. of the connected
Ethernet module.
(Default: blank)
1 to 64
Type SIEMENS S7 (fixed)
SIEMENS S7
(fixed)
IP Address
Set the IP address of the connected
Ethernet module.
(Default: blank)
PLC side IP
address
FETCH Port
No.
Set the FETCH port No. of the
connected Ethernet module.
(Default: 2000)
1024 to 65534
WRITE Port No.
For the WRITE port No. of the
connected Ethernet module, the
value that the FETCH port No. is
incremented by one is set
automatically.
(Default: 2001)
1025 to 65535
Communication TCP (fixed) TCP (fixed)