Specifications

15. CONNECTION TO SIEMENS PLC
15.2 Serial Connection
15 - 9
CONNECTION TO SIEMENS PLC
15
15.2.7 Connecting to SIMATIC S7-
200
Communication settings
Set the communication settings of PLC and PC/PPI
cable.
(1) PLC settings
Set the communication settings of PLC by operating
the SIEMENS programming tool(STEP7-WIN32).
*1 Adjust the settings with GOT settings.
*2 Set the address without overlapping the address of other
units.
(2) PC/PPI cable settings
Set the transmission speed by operating the DIP switch
on the PC/PPI cable.
*1 Adjust with GOT settings.
15.2.8 Precautions
GOT alarm list (system alarm) function
Error information cannot be monitored when the GOT is
connected to a SIEMENS PLC.
(The error information on the PLC CPU side can be
monitored.)
For details on the alarm list (system alarm), refer to the
following manual:
GT Designer3 (GOT2000) Help
(1) When powering ON the system
Turn ON all PLC CPUs before turning ON the GOT.
If the GOT is turned ON before power-up of the PLC
CPUs, restart the GOT.
(2) When powering OFF a PLC CPU at another station
When a PLC CPU at another station (the PLC CPU to
which the HMI Adapter is not connected) is turned OFF,
monitoring by the GOT is stopped.
To resume the monitoring, restart the GOT.
(Monitoring will not be resumed on GOT even if the
PLC CPU is turned ON again.)
Setting item PLC Side Setting
Transmission speed
*1
9600bps, 19200bps
Data bit 8bits (fixed)
Parity bit Even (fixed)
Stop bit 1bit (fixed)
Host address
*2
1 to 31
SWITCH
1
SWITCH
2
SWITCH
3
SWITCH
4
SWITCH
5
Transmission
speed
00100
19200bps
*1
01000
9600bps
*1
S7-200 CPU
RS-485
RS-232
PC/PPI cable
DIP switch
(down side:0, upper side:1)
1
0
12345
1
0
SWITCH 123
SWITCH 4
SWITCH 5