Specifications
10. CONNECTION TO ALLEN-BRADLEY PLC
10.3 Ethernet Connection
10 - 17
CONNECTION TO ALLEN-BRADLEY PLC
10
GOT Ethernet setting
Ethernet setting
(1) Ethernet connection type: EtherNet/IP (AB)
This section describes the Ethernet setting for the
communication driver AB Control/CompactLogix.
*1 Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
■ Communication detail settings
Item Description Range
GOT IP Address
Set the IP address of the GOT.
(Default: 192.168.0.18)
0.0.0.0 to
255.255.255.255
Subnet Mask
Set the subnet mask for the sub
network.(Only for connection via
router)
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
0.0.0.0 to
255.255.255.255
Default
Gateway
Set the router address of the
default gateway where the GOT is
connected.(Only for connection
via router)
(Default: 0.0.0.0)
0.0.0.0 to
255.255.255.255
Peripheral S/W
Communication
Port No.
Set the GOT port No. for the S/W
communication.
(Default: 5015)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
Transparent Port
No.
Set the GOT port No. for the
transparent function.
(Default: 5014)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
Item Description Set value
Host
The host is displayed.(The host is
indicated with an asterisk (*).)
―
Net No.
Set the network No. of the connected
Ethernet module.
(Default: blank)
1 to 239
Station
*1
Set the station No. of the connected
Ethernet module.
(Default: blank)
1 to 64
Type AB(EtherNet/IP) (fixed)
AB(EtherNet/
IP) (fixed)
IP address
Set the IP address of the connected
Ethernet module.
(Default: blank)
PLC side IP
address
Port No. 44818 (fixed) 44818 (fixed)
Communication
format
TCP (fixed) TCP (fixed)
Slot No.
Set the slot No. of the PLC to which
the Ethernet module is connected.
(Default: blank)
0 to 16