Specifications

10. CONNECTION TO ALLEN-BRADLEY PLC
10.2 Serial Connection
10 - 13
CONNECTION TO ALLEN-BRADLEY PLC
10
10.2.6 PLC Side Setting
POINTPOINTPOINT
ALLEN-BRADLEY PLC
For details of ALLEN-BRADLEY PLCs, refer to the
following manuals.
ALLEN-BRADLEY PLC user's Manual
Directly connecting to the CPU
*1 Set the Baud Rate according to the transmission speed
setting on the GOT side.
For the transmission speed setting on the GOT side, refer to
the following.
10.2.5 Communication detail settings
*2 Set the Error Detection according to the sum check format
setting on the GOT side.
For the sum check format setting on the GOT side, refer to
the following.
10.2.5 Communication detail settings
Connecting to DH485 network via adapter
(1770-KF3) (Setting of Adapter)
*1 Set the Baud Rate according to the transmission speed
setting on the GOT side.
For the transmission speed setting on the GOT side, refer to
the following.
10.2.5 Communication detail settings
*2 Set the Error Detection according to the sum check format
setting on the GOT side.
For the sum check format setting on the GOT side, refer to
the following.
10.2.5 Communication detail settings
*3 For the Maximum Node Address, set the same address as
the Maximum Node Address on the DH-485 network.
*4 Set the DH-485 Node Address according to the Host
Address on the GOT side.
Set a unique DH-485 Node Address so that it does not
conflict with the Node Address of the PLC CPU on the DH-
485 network.
For the Host Address setting on the GOT side, refer to the
following.
10.2.5 Communication detail settings
Item
Setting details
SLC500
Series
MicroLogix
1000/1200/
1500 Series
Control/
Compact/
FlexLogix
Series
Baud Rate
*1
4800bps,
9600bps,
19200bps
4800bps,
9600bps,
19200bps,
38400bps
4800bps,
9600bps,
19200bps,
38400bps
Parity EVEN NONE NONE
Control Line NO HANDSHAKING
Communication
Driver
DF1 HALF-DUPLEX SLAVE
Duplicate Packet
Detection
DISABLE
Station Address 0
Error Detection BCC
BCC, CRC
*2
BCC, CRC
*2
Item Setting details
Baud Rate
*1
4800bps, 9600bps, 19200bps
Parity Even
Flow Control Disable (No Handshaking)
DF1 Device
Category
DF1 half-duplex slave, local mode
Error Detection
*2
BCC
DH-485 Baud Rate 19200bps
Maximum Node
Address
1 to 31
*3
DH-485 Node
Address
0 to 31
*4