Specifications

9 - 50
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
(2) DIP switch setting (SW3)
Set the communication speed and the data bit
configuration using the DIP switch (SW3).
(3) DIP switch settings (SW4)
Set the communication specifications and the
termination resistor using the DIP switch (SW4).
9.5.18 Station number setting
Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
(1) Direct specification
The station number setting range of the temperature
controller side differs from that of the GOT side.
Specify the station No. of the temperature controller to
be changed when setting devices referring the following
table.
Setting item Set value
Switch position
1 2 3 4 5 6 7 8
Communication
speed
4800bps OFF OFF
-
9600bps ON OFF
19200bps OFF ON
38400bps ON ON
Data bit
configuration
Data bit:
8 bits,
Parity:
None,
Stop: 2
bits
-OFFOFF -
Data bit:
8 bits,
Parity:
None,
Stop: 1 bit
-ONOFF -
Data bit:
8 bits,
Parity:
Even,
Stop: 1 bit
-OFFON -
Data bit:
8 bits,
Parity:
Odd,
Stop: 1 bit
-ONON -
Setting item Set value
Switch position
1 2 3 4
Communication
specification
setting
RS-422A OFF OFF -
RS485 ON ON -
Termination
resistor setting
Enable - ON
Disable - OFF
1 2 3 4 5 6 7 8
ON
OFF ON
Dip switch(SW3)
1
ON
342
OFF
ON
Dip switch(SW4)
Temperature
controller
Module address
setting of
temperature
controller side
GOT side
station
number
setting
Remark
H-PCP-J
H-PCP-A
H-PCP-B
Z-TIO
Z-COM
0 to F
(Hexadecimal)
1 to 16
(Decimal)
The GOT side station
number setting is the module
address setting value +1.
Z-DIO
0 to F
(Hexadecimal)
17 to 32
(Decimal)
The GOT side station
number setting is the module
address setting value +17.
Z-CT
0 to F
(Hexadecimal)
33 to 48
(Decimal)
The GOT side station
number setting is the module
address setting value +33.
X-TIO
1 to 99
(Decimal)
2 to 100
(Decimal)
The GOT side station
number setting is the module
address setting value +1.
CB, FB, RB,
PF, AG, HA,
MA, RMC,
THV, SA, SB1
1 to 99
(Decimal)
1 to 99
(Decimal)
The GOT side station
number setting is the same
as the module address
setting value.
B400
1 to 99
(Decimal)
1 to 99
(Decimal)
The GOT side station
number is the module
address setting value +1 or
+2.
GOT
Station
No.10
Station
No.3
Station
No.1
Station
No.15
Station
No.6
Examples of station number setting