Specifications
9 - 48
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
9.5.14 Connecting to SA100/SA200
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1 Adjust the settings with GOT settings.
*2 Select the device address1 without overlapping with that of
other units.
*3 Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4 When the setting value is set to 0, a communication is not
made.
9.5.15 Connecting to X-TIO Module
(1) Communication settings
Make the communication settings of the temperature
controller.
*1 Adjust the settings with GOT settings.
*2 When the setting value is set to 0, a communication is not
made.
(2) Setting DIP switches
Make the settings of transmission speed, data bit
configuration, communication protocol.
(3) Module address settings
Set the unit address using the rotary switch (address
setting switch).
Item Setting range
Communication speed
*1
9600bps, 19200bps
Data bit configuration
*1
(Data bit, Parity bit, Stop bit)
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
Device address
*2
(Slave address)
1 to 99
*4
Interval time
*3
0 to 250 (ms)
Item Setting range
Communication speed
*1
9600bps, 19200bps, 38400bps
Communication protocol MODBUS
Data bit configuration
Data bit: 8bit, Parity: None
Data bit: 8bit, Parity: Even
Data bit: 8bit, Parity: Odd
Stop bit: 1bit (fixed)
Module address
*2
1 to 99
Internal data bus
terminating resistor
When combining the module, turn ON the
internal data bus terminating resistor at both
ends of the module.
Data interval extension
time
0 to 99ms
Setting item Set value
Switch position
1 2 3 4 5 6 7 8
Communicati
on speed
9600bps ON OFF
19200bps OFF ON
38400bps ON ON
Data bit
configuration
Data bit: 8bit,
Parity: None
ON OFF OFF
Data bit: 8bit,
Parity: Even
ON OFF ON
Data bit: 8bit,
Parity: Odd
ON ON ON
Communicati
on protocol
MODBUS ON
Internal data
bus
termination
resistor
setting
OFF OFF
ON ON
Data interval
extension
time
0 to 99ms ON OFF ON
12345678
ON
12345678
ON
OFF
Dip switch
5
4
3
2
1
0
9
8
7
6
5
5
4
3
2
1
0
9
8
7
6
5
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
5
4
3
2
1
0
9
8
7
6
5
5
4
3
2
1
0
9
8
7
6
5
Upper digit setting
(Set value x10)
Lower digit setting
(Set value x1)
Rotary switch
(Address setting switch)